882

The 800 series are 2-wire conventional low profile plug-in detectors designed to meet the performance criteria designated by UL. It is a low cost and high reliability series. A LED will be latched on to locally indicate alarm. The in (-) and out (-) terminals are short-circuited inside the detectors. When the detector is mounted , it will continue the wire to the next device or EOL resistor. When it is removed, the wire will be open for wiring supervision.

Categories: ,

Description

  • Provides the 360° visibility of alarm indication
  • Dual LED indicators on symmetrical sides
  • Sealed against entry of moisture

 

Operating Temperature Range:  32°F to 100°F (0°C to 38°C) for heat, 32°F to 120°F (0°C to 49°C) for lonization, photoelectronic
Operating Humidity Range: 5%-95% RH
Latching Alarm: Reset by momentary power interruption
Max Air Velocity: < 4,000ft/min (Photoelectronic), 2000ft/min (Ionization)
Operating Voltage: 15 ~ 30VDC
Standby Current: 50 µA
Alarm Current: min 2mA @ 3.1VDC – max 80mA @ 6.5VDC
Maximum Ripple Voltage: 4 Volts peak to peak
Sensitivity: 145°F (63°C) heat only